4-channel RTD/resistance input module
4-channel RTD/resistance input module
- Catalog Number
- 1762-IR4
- Product Family
- MicroLogix Expansion I/O Modules
- Platform
- Chassis-Based I/O
- Category
- I/O
- Product Type
- RTD / Temperature

4-channel RTD/resistance input module
| Input type | 604 Ω Nickel-Iron 518 |
| Input signal, configurable | True |
| Output signal configurable | False |
| Number Of Channels | 4 point |
| Channel to channel isolation | ±10V DC |
| Input channel configuration | Via configuration software screen or the user prog (by writing a unique bit pattern into the module’s configuration file) |
| Channel diagnostics | Over or under range or open circuit condition by bit reporting for analog inputs |
| Input, voltage | False |
| Output, voltage | False |
| Bus current draw | 50mA @ 24V DC, maximum |
| Excitation current source | 0.5 mA and 1.0 mA selectable per channel |
| Input, current | False |
| Output, current | False |
| Power supply distance rating | 6 (the module may not be more than 6 modules away from the system power supply) |
| I/O Isolation | Isolated |
| Input and output group to system isolation | 30V AC/30V DC working voltage type test: 500V AC or 707V DC @ 1min |
Interfaces field sensors and actuators with the controller at local or distributed I/O stations.
Check signal type, channel count, voltage/current, isolation, terminal base and environmental requirements.
Plan adapter, power segmentation, addressing, wiring, diagnostics and channel configuration before commissioning.
Create an old-to-new I/O mapping and validate electrical characteristics and field behavior channel by channel.
DS Robotik evaluates product selection together with field conditions and system architecture, covering PLC/I/O architecture, panels, software, integration, commissioning and modernization.
Allen-Bradley 1762-IR4 is part of the MicroLogix Expansion I/O Modules product family on the Chassis-Based I/O platform.